Fault code
on the dis-
play
System characteris-
tics
Cause Measures
59 No DHW heating Lead break, outlet
temperature sen-
sor
Check sensors (see
page 96)
92 No DHW heating Short circuit, col-
lector temperature
sensor; connection
to the solar control
module
Check sensor & on the
solar control module.
94 No DHW heating Short circuit, cylin-
der temperature
sensor; connection
to the solar control
module
Check sensor % on the
solar control module.
9A No DHW heating Lead break, collec-
tor temperature
sensor; connection
to the solar control
module
Check sensor & on the
solar control module.
9C No DHW heating Lead break, cylin-
der temperature
sensor; connection
to the solar control
module
Check sensor % on the
solar control module.
9E Control mode No flow rate in the
collector circuit or
flow rate too low, or
temperature limiter
has responded
Check solar circuit pump
and solar circuit. Acknowl-
edge fault message.
9F Control mode Solar control mod-
ule fault
Check solar control mod-
ule
A7 Control mode as per
delivered condition
Faulty program-
ming unit
Replace programming
unit
A8 Burner blocked The
venting program is
started automatically
(see page 61)
Air lock in the inter-
nal circulation
pump or minimum
flow rate not ach-
ieved
Vent the system if the fault
message continues to be
displayed
Troubleshooting
Fault codes
(cont.)