External heating program changeover
The "External heating program change-
over" function is connected via external
extension input "
aVD
". You can select
which heating circuits the heating pro-
gram changeover affects in coding
address "91":
Heating program changeover Coding
No changeover 91:0
Heating circuit without mixer A1 91:1
Heating circuit with mixer M2 91:2
Heating circuit without mixer and heating circuit with mixer 91:3
You can select in which direction the
heating program changes over in coding
address "D5":
Heating program changeover Coding
Changeover towards "Permanently reduced" or "Permanent
standby" mode (subject to the selected set value)
d5:0
Changeover towards "Constant heating mode" d5:1
The duration of the heating program
changeover can be adjusted in coding
address "F2":
Heating program changeover Coding
No heating program changeover F2:0
Duration of the heating program changeover 1 to 12 hours F2:1 to
F2:12
The heating program changeover stays
enabled for as long as the contact
remains closed, but at least as long as
the duration selected in coding address
"F2".
Function description
Control functions
5418 193 GB