Removing the front panels
See page 10, steps 1 to 5.
Filling the heating system
!
Please note
Unsuitable fill water increases the level of deposits and corrosion and may
lead to boiler damage.
Thoroughly flush the entire heating system prior to filling it with water.
Only use fill water of potable quality.
Soften fill water with hardness exceeding 300ppm (3.0 mmol/l), e.g. use a
small softening system for heating water (see Vitoset price list).
An antifreeze additive suitable for heating systems can be mixed with the
fill water.
Shown with connection set for finished walls (accessory)
1. Check the pre-charge pressure of the
diaphragm expansion vessel.
2. Close the gas shut-off valve.
3. Fill heating system via boiler fill &
drain valve
A
in the heating return
(at the connection set on the side or
above the boiler). (Minimum system
pressure > 1.0 bar).
Commissioning, inspection, maintenance
Further details regarding the individual steps
5418 193 GB