
47
Checking the combustion quality
The electronic combustion control unit automatically ensures an optimum combustion
quality. Only the combustion values need to be checked during commissioning and
maintenance. For this, check the CO
2
or O
2
content. For a function description of the
electronic combustion control unit, see page 119.
!
Please note
To prevent operating faults and equipment damage,
never operate with dirty combustion air.
CO
2
or O
2
content
■ The CO
2
content must be within the following ranges (upper and lower output):
– 7.7 to 9.2% for natural gas H
– 9.3 to 10.9% for LPG P
■ For all gas types, the O
2
content must be between 4.4% and 6.9%.
If the actual CO
2
or O
2
values lie outside their respective ranges, proceed with the
following steps:
■ Check the balanced flue system for tightness, see page 34.
■ Check the ionisation electrode and connecting cable, see page 37.
Note
During commissioning, the combustion control unit carries out an automatic calibra-
tion. Only test the emissions approx. 30 s after the burner has started.
1. Connect a flue gas analyser at flue
gas port
A
on the boiler flue con-
nection.
2. Open the gas shut-off valve, start the
boiler and create a heat demand.
3. Select the lower output (see
page 48).
4. Check the CO
2
content. Should the
actual value deviate from the above
ranges by more than 1%, implement
steps from page 47.
5. Enter actual values into the service
report.
6. Select the upper output (see
page 48).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5418 193 GB
Service
Comments to this Manuals