7. Check the CO
2
content. Should the
actual value deviate from the above
ranges by more than 1%, implement
steps from page 47.
8. After testing, press OK.
9. Enter actual values into the service
report.
To set the upper/lower output:
1. Press OK and simultaneously for
approx. 4 s.
2. "Actuator test"
3. Select the lower output:
Select "Base load" "ON" and con-
firm with OK.
4. Select the upper output:
Select "Full load" "ON" and confirm
with OK.
Matching the control unit to the heating system
Subject to the equipment level, the control unit must be matched to the system. Var-
ious system components are recognised automatically by the control unit and the
relevant codes are adjusted automatically.
For the selection of an appropriate design, see the following diagrams.
For coding steps, see page 61.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)