70
Coding in the delivered condition Possible change
Flow temperature maximum limit
C6:74 Electronic maximum flow
temperature limit set to
74 °C
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C (limited
by boiler-specific parame-
ters)
Heating program changeover
d5:0 External heating program
changeover changes to
"Constant operation with
reduced room tempera-
ture"
d5:1 The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture"
Max. pump speed in standard mode
E6:65 Maximum speed of the
variable speed heating
circuit pump: 65 % of the
maximum speed
E6:0
to
E6:100
Maximum speed adjusta-
ble from 0 to 100%
Min. pump speed
E7:30 Minimum speed of the
variable speed heating
circuit pump: 30 %
E7:0
to
E7:100
Minimum speed adjustable
from 0 to 100% of the max-
imum speed
Screed function
F1:0 Screed function disabled F1:1
to
F1:6
Screed drying function
adjustable in accordance
with 6 optional tempera-
ture/time profiles (see
page 114)
F1:15 Constant flow temperature
20 °C
Party mode time limit
F2:8 Time limit for party mode
or external heating pro-
gram changeover via key:
8 h
*1
F2:0 No time limit for party
mode
*1
F2:1
to
F2:12
Time limit adjustable from 1
to 12h
*1
*1
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
Code 1
Heating circuit 1/heating circuit 2
(cont.)
5418 193 GB