80
Coding in the delivered condition Possible change
b2:8 With remote control and
for the heating circuit,
operation with room tem-
perature hook-up must be
programmed: Room influ-
ence factor 8 (change
code only for heating cir-
cuit with mixer)
b2:0 Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
d3:14 Heating curve slope =
1.4
d3:2
to
d3:35
Heating curve slope adjust-
able from 0.2 to 3.5 (see
page 54)
d4:0 Heating curve level = 0 d4:–13
to
d4:40
Heating curve level adjust-
able from –13 to 40 (see
page 54)
E1:1 With remote control: Set
value for standard room
temperature adjustable at
the remote control from
10 to 30 °C
E1:0 Set value for standard
room temperature, adjust-
able from 3 to 23 °C
E1:2 Set value for standard
room temperature, adjust-
able from 17 to 37 °C
E2:50 With remote control: No
display correction of the
actual room temperature
E2:0
to
E2:49
Display correction –5 K
to
Display correction –0.1 K
E2:51
to
E2:99
Display correction +0.1 K
to
Display correction +4.9 K
E5:0 Without external, variable
speed heating circuit
pump
E5:1 With external variable
speed heating circuit pump
(automatic recognition)
E8:1 Minimum speed in opera-
tion with reduced room
temperature subject to
the setting of coding
address "E9"
E8:0 Speed subject to the set-
ting in coding address
"E7"
E9:45 Speed of the variable
speed heating circuit
pump: 45% of the maxi-
mum speed in operation
with reduced room tem-
perature
E9:0
to
E9:100
Speed adjustable from 0 to
100% of the maximum
speed during operation
with reduced room temper-
ature
Code 2
Heating circuit 1/heating circuit 2
(cont.)
5418 193 GB