Vitotronic 200 and 300-K Installation and Service
Troubleshooting
Fault Display Vitotronic 300-K (continued)
Fault codes
Displayed fault code System characteristics Cause Measures
94 No solar DHW heating. Short circuit, DHW tank
temperature sensor, connection
of temperature sensor % at
solar control module or sensor
at S2 of the Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).
98 Control mode. Lead break, temperature sensor
/, connection to solar control
module.
Check temperature sensor /
(see separate installation and
service instructions).
Check coding address 20
in “Solar” group.
99 Control mode. Lead break, temperature sensor
, connection to solar control
module.
Check temperature sensor
(see separate installation and
service instructions).
Check coding address 20
in “Solar” group.
9A No solar DHW heating. Lead break, collector
temperature sensor, connection,
temperature sensor & at solar
control module or sensor at S1
of the Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).
9B Control mode. Lead break, temperature
sensor, connection at S3 of the
Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).
9C No solar DHW heating. Lead break, DHW tank
temperature sensor, connection
of temperature sensor % at
solar control module or sensor
at S2 of the Vitosolic.
Check sensor at the solar
control unit (see separate
installation and service
instructions).
9E Control mode. No flow rate in solar circuit
or flow rate too low, or
temperature limiter has
responded.
Check solar circuit.
Acknowledge fault message
(see separate installation and
service instructions).
9F Control mode. Solar control module
or Vitosolic faulty.
Displayed if a fault occurs at
these devices that has no fault
code in the Vitotronic.
Check solar control unit (see
separate installation and service
instructions).
AB Control operation, DHW
tank may be cold.
Primary store system
configuration error:
Code “55:3” has been selected,
but plug aJB is not plugged
in and/or Codes “4C:1” and
“4E:2” have not been set.
Insert plug aJB and check
coding.
B1 Control mode. Communication error,
programming unit
Check connections and replace
the programming unit if
required.
B5 Control mode. Internal fault Check correct insertion
of PCB (see parts list).