Viessmann VITOTRONIC 300-K Operations Instructions Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
Vitotronic 200 and 300-K Installation and Service
5693 976 - 04
50
“General” Group
Value address
00: ...
System version Description
2 1 One heating circuit without mixing valve A1 (heating circuit 1),
with DHW heating (code is adjusted automatically)
3 2 One heating circuit with mixing valve M2 (heating circuit 2),
without DHW heating
4 2 One heating circuit with mixing valve (heating circuit 2),
with DHW heating
5 3 One heating circuit without mixing valve A1 (heating circuit 1) and one heating circuit
with mixing valve M2 (heating circuit 2),
without DHW heating (code is adjusted automatically)
6 3 One heating circuit without mixing valve A1 (heating circuit 1) and one heating circuit
with mixing valve M2 (heating circuit 2),
with DHW heating (code is adjusted automatically)
7 3 One heating circuit with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), without DHW heating
8 3 One heating circuit with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), with DHW heating
9 3 One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit
with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), without DHW heating (code is adjusted
automatically)
10 3 One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit
with mixing valve M2 (heating circuit 2) and one heating circuit
with mixing valve M3 (heating circuit 3), with DHW heating (code is adjusted
automatically)
Coding
Coding in the factory set condition Possible change
00:1 System version 1:
One heating circuit without mixing valve A1
(heating circuit 1), without DHW heating
00:2
to
00:10
For system schemes, see the following table:
Coding in the factory set condition Possible change
12:5 With extension EA1:
DHW recirculation pump runtime for brief
operation: 5 min.
12:1
to
12:60
Runtime adjustable from 1 to 60 min.
1E:0 With extension EA1 (analogue input 0-10V):
Temperature demand from 32 to 212°F
(0 to 100°C):
1V
50°F (10°C)
10V 212°F (100°C)
1E:1 Temperature demand from
86 to 248°F (30 to 120°C):
1V 86°F (30°C)
10V 248°F (120°C)
4A:0 Never adjust. - -
4B:0
Sensor aJB not installed.
4B:1
Sensor aJB installed (e.g. temperature sensor T2);
will be recognized automatically.
4C:0
Connection at plug A1:
heating circuit pump.
4C:1 Primary pump, primary store system.
4F:5 Distribution pump run-on time 5 min. 4F:0 No pump run-on.
4F:1
to
4F:60
Run-on time adjustable from 1 to 60 min.
Coding 2 Vitotronic 300-K
Page view 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 95 96

Comments to this Manuals

No comments