Vitotronic 200 and 300-K Installation and Service
Function Description, Vitotronic 300-K
Heating Circuit Control (continued)
System dynamics mixing valve circuit
You can influence the control characteristics of the mixing
valve via coding address “C4”.
Central control
Central control for a heating circuit can be programmed
via coding address “7A” in the “General” group.
The heating and holiday program then applies to all
additional heating circuits of the system.
For these heating circuits, when the heating and holiday
program is enabled, “Central control” is displayed.
Any holiday programs that may have been set will be
deleted.
Party and economy modes cannot be enabled on all
control units.
Differential temperature:
The differential temperature is adjustable via coding
address “9F” in the “General” group, factory set
condition: 8 K.
The differential temperature is the minimum value by
which the boiler water temperature should be higher
than the highest currently required supply temperature
of the heating circuit with mixing valve.
H System with only one heating circuit with mixing valve:
The set boiler water temperature will be automatically
regulated to 8 K above the set supply temperature.
H System with heating circuit without mixing valve
and heating circuit with mixing valve: The set boiler
water temperature operates in accordance with a
special heating curve. The differential temperature of
8 K towards the set supply temperature is set at the
factory.
Legend
A Max. boiler water temperature
B Slope = 1.8 for heating circuit without mixing valve
C Slope = 1.2 for heating circuit with mixing valve
D Boiler water temperature (with a differential
temperature = 8 K)
E Lower boiler water temperature, defaulted by the
boiler coding card
Supply temperature control
Frost protection
The supply temperature is maintained in accordance with
the heating curve for the reduced set room temperature,
but at min. 50°F (10°C).
A variable frost limit can be set in accordance with coding
address “A3” in the “Heating circuit...” group.
Example using the settings in the factory set condition
Legend
A Heating curve for operation with standard room
temperature
B Heating curve for operation with reduced room
temperature
Boiler water or
Supply temperature
Outside temp.
Set room temperature
Outside temperature
Supply temperature