  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 46
47
5693 976 - 04
Vitotronic 200 and 300-K Installation and Service
“General” Group
Coding
Coding in the factory setting Possible change
53:1
Function connection sK of the
internal extension:
DHW recirculation pump
53:0
Function connection sK: Central
fault message.
53:2
Function connection sK:
External heating circuit pump
(heating circuit 1).
53:3
Function connection sK:
External circulation pump for
DHW tank heating.
76:2 With cascade communication
module (recognized
automatically; only for constant
temperature control units).
76:1 With LON communication module
(recognized automatically).
76:0 Without communication module
80:6 A fault message is displayed
if a fault is active for at least
30 seconds
80:0 Immediate fault message.
80:2
to
80:199
Minimum fault duration until fault
message occurs, adjustable from
10 sec. to 995 sec; 1 step 5 sec.
81:1 Automatic summer/wintertime
changeover
81:0 Manual summer/wintertime
changeover.
81:2 Use of the radio clock receiver
(automatic recognition).
81:3 With LON communication
module: The control unit receives
the time.
88:0 Temperature display in °C
(Celsius)
88:1 Temperature display in °F
(Fahrenheit).
8A:175 Do not adjust. -- --
8F:0 Operation in the standard
menu and extended
menu enabled
Note: The respective code is
only activated when you
exit the service menu
8F:1 Operation in the standard
menu and extended menu
blocked.
Emissions test mode can
be enabled
8F:2 Operation enabled in the
standard menu; blocked in
the extended menu.
Emissions test mode can
be enabled
94:0 Without Open Therm extension 94:1 With Open Therm extension
(automatic recognition).
95:0 Without Vitocom 100
communication interface
95:1 With Vitocom 100
communication interface
(automatic recognition).
99:0 Do not adjust -- --
9A:0 Do not adjust -- --
9B:70 Set supply temperature for
external demand 158°F (70°C)
9B:0
to
9B:127
Set supply temperature for
external demand adjustable
from 32 to 260°F (0 to 127°C)
(limited by boiler-specific
parameters).
Coding 2 Vitotronic 200