Vitotronic 200 and 300-K Installation and Service
5693 976 - 04
76
Troubleshooting
Fault Display Vitotronic 300-K (continued)
Fault codes
Displayed fault code System characteristics Cause Measures
B6 Constant mode. Invalid hardware recognized Check coding address
“92” in “General” group;
“92:166” must be selected.
Note: Code “8A:176” must be
selected for coding address
“92” to be displayed.
BA Mixing valve “Closed”. Communication error,
PCB extension for heating
circuits 2 and 3 with mixing
valve
Check insertion of PCB and ribbon
cable; replace PCB if required.
BC Control mode without
remote control.
Communication error,
remote control Vitotrol
heating circuit without
mixing valve A1 (heating
circuit 1)
Check connections for cable
(see separate installation and service
instructions) and coding address “A0”
in the “Heating circuit...” group.
BD Control mode without
remote control.
Communication error,
remote control Vitotrol
heating circuit with mixing
valve M2 (heating circuit 2)
Check connections for cable
(see separate installation and service
instructions) and coding address “A0”
in the “Heating circuit...” group.
BE Control mode without
remote control.
Communication error,
remote control Vitotrol
heating circuit with mixing
valve M3 (heating circuit 3)
Check connections for cable
(see separate installation and service
instructions) and coding address “A0”
in the “Heating circuit...” group.
BF Control mode.
No communication via
LON.
Incorrect LON
communication module
Replace LON communication module.
C2 Control mode. Lead break, KM
BUS to solar control module
or Vitosolic
Check KM BUS cable and device.
Without solar control unit:
Set code “54:0” in the “General”
group.
CF Control mode.
No communication via
LON.
LON communication
module fault
Check LON communication module
and replace if required.
D3 Control mode. Communication error
extension EA1
Check connections
(see page 93).
Without extension EA1:
Set code “5B:0” in the “General”
group.
D5 Boiler ramps up to
electronic maximum
boiler water temperature
limit.
The boiler does not “log in”
at the cascade control unit.
Check communication via participant
check, lines
to Vitotronic 200 and codes
D6 Control mode. Input DE1 at extension
EA1 reports a fault
Remove fault at appliance concerned.
D7 Control mode. Input DE2 at extension
EA1 reports a fault
Remove fault at appliance concerned.
D8 Control mode. Input DE3 at extension EA1
reports a fault
Remove fault at appliance concerned.