Vitotronic 200 and 300-K Installation and Service
“Solar” Group
Coding
Coding in the factory set condition Possible change
Speed control solar circuit pump
02:0 Solar circuit pump (multi stage) without speed
control by solar control module SM1.
02:1 Solar circuit pump (multi stage) is speed-
controlled with wave pack control.
02:2 Solar circuit pump is speed-controlled with PWM
control.
DHW tank maximum temperature
08:60 The solar circuit pump stops when the actual
DHW temperature reaches the maximum
DHW tank temperature 140°F (60°C).
08:10
to
08:90
The maximum DHW tank temperature
is adjustable from 50 to 194°F (10 to 90°C).
Stagnation time reduction
0A:5 To protect system components and heat
transfer medium: the speed of the solar
circuit pump is reduced if the actual DHW
temperature is 5 K below the maximum DHW
tank temperature.
0A:0 Stagnation time reduction is disabled.
0A:1
to
0A:40
Value for stagnation time reduction is adjustable
from 1 to 40 K.
Flow rate solar circuit
0F:70 The solar circuit flow rate at maximum pump
speed is 1.8 GPM (7 L/min).
0F:1
to
0F:255
Flow rate adjustable from 0.02 to 6.76 GPM
(0.1 to 25.5 L/min);
1 step
0.02 GPM (0.1 L/min).
20:0 No extended control functions enabled. 20:1 Additional function for DHW heating.
20:2 Differential temperature control 2.
20:3 Differential temperature control 2 and auxiliary
function.
20:4 Differential temperature control 2 for central
heating backup.
20:5 Thermostat function.
20:6 Thermostat function and auxiliary function.
20:7 Solar heating via external heat exchanger
without additional temperature sensor.
20:8 Solar heating via external heat exchanger
with additional temperature sensor.
20:9 Solar heating of two DHW tanks.
Note: The solar group is only displayed if a solar control
module, type SM1, is connected.
Coding 1 Vitotronic 300-K