Vitotronic 200 and 300-K Installation and Service
“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)
Coding in the factory set condition Possible change
C0:0 With remote control:
Without shutdown time optimization
C0:1 With shutdown time optimization
(max. offset 1 h)
C0:2 With shutdown time optimization
(max. offset 2 h)
C1:0 With remote control:
Without shutdown time optimization
C1:1
to
C1:12
With shutdown time optimization
(max. offset 10 to 120 min.)
1 step
10 min.
C2:0 With remote control:
Without learning shutdown time optimization
C2:1 With learning shutdown time optimization
C3:125 Mixing valve runtime 125 sec. C3:10 C3:10
to
C3:255
Runtime adjustable from 10 to 255 sec.
C4:1 System dynamics
Mixing valve control characteristics
C4:0
to
C4:3
Controller responds too quickly
(cycles between “Open” and “Closed”):
Select a lower value
Controller responds too slowly
(temperature is not held sufficiently):
Select a higher value
C5:20 Electronic minimum supply temperature limit 68°F
(20°C)
C5:1
to
C5:127
Minimum limit adjustable from 34 to 261°F
(1 to 127°C)
(only for operation with standard room
temperature)
C6:74 Electronic maximum supply temperature limit
set to 165°F (74°C)
C6:10
to
C6:127
Maximum limit adjustable from 50 to 261°F
(10 to 127°C) (limited by boiler-specific
parameters)
C8:31 With remote control unit and for the heating
circuit, operation with room temperature hook-
up must be programmed:
Without room influence
C8:1
to
C8:30
Room influence limit adjustable from 1 to 30 K
D5:0 With external heating program changeover
(observe setting for coding addresses “5D”,
“5E” and “5F” in the “General” group):
Heating program switches to “Constant central
heating with reduced room temperature”
or “Standby mode” (subject to the settings
of the set reduced room temperature).
D5:1 The heating program changes to “Constant
operation with standard room temperature”.
D8:0 No heating program changeover via extension
EA1
D8:1 Heating program changeover via input DE1
at extension EA1
D8:2 Heating program changeover via input DE2
at extension EA1
D8:3 Heating program changeover via input DE3
at extension EA1
E1:1 With remote control:
Set day temperature adjustable at the remote
control unit from 50 to 86°F (10 to 30ºC).
E1:0 Set day temperature adjustable from 37 to 73°F
(3 to 23ºC).
E1:2 Set day temperature adjustable from 63 to 99°F
(17 to 37ºC).
E2:50 With remote control:
No display correction of the actual room
temperature.
E2:0
to
E2:49
Display correction –5 K
to
Display correction –0.1 K
E2:51
to
E2:99
Display correction +0.1 K
to
Display correction +4.9 K
Coding 2 Vitotronic 300-K