Vitotronic 200 and 300-K Installation and Service
5693 976 - 04
62
“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group
Coding
Coding in the factory set condition Possible change
A0:0 Without remote control A0:1 With Vitotrol 200A (automatic recognition)
A0:2 With Vitotrol 300A or Vitohome 300
(automatic recognition)
A1:0 All possible settings at the remote control
can be accessed
A1:1 Only party mode can be set at the remote
control (only for Vitotrol 200A)
A2:2 DHW tank priority applicable to heating circuit
pump and mixing valve
A2:0 Without DHW tank priority applicable
to heating circuit pump and mixing valve
A2:1 DHW tank priority only applicable to mixing
valve
A2:3
to
A2:15
No function.
A3:2 Outside temperature below 34°F (1°C):
Heating circuit pump “ON”
Outside temperature above 37°F (3°C):
Heating circuit pump “OFF”
A3:-9
to
A3:15
Heating circuit pump “ON/ OFF”
(see the following table)
Note: If a value below 34°F (1°C) is selected, there is a
risk that pipes outside the thermal insulation of the
building could freeze up.
The standby mode in particular should be taken into
consideration, e.g. during holidays.
Parameter address
A3:...
Heating circuit pump
Heating circuit pump “ON” Heating circuit pump “OFF”
-9 14°F (–10°C) 18°F (–8°C)
-8 16°F (–9°C) 19.5°F (–7°C)
-7 18°F (–8°C) 21°F (–6°C)
-6 19.5°F (–7°C) 23°F (–5°C)
-5 21°F (–6°C) 25°F (–4°C)
-4 23°F (–5°C) 27°F (–3°C)
-3 25°F (–4°C) 28.5°F (–2°C)
-2 27°F (–3°C) 30°F (–1°C)
-1 28.5°F (–2°C) 32°F (0°C)
0 30°F (–1°C) 34°F (+1°C)
1 32°F (0°C) 36°F (+2°C)
2
to
15
34°F (+1°C)
to
57°F (+14°C)
27°F (+3°C)
to
61°F (+16°C)
Coding 2 Vitotronic 300-K