Viessmann VITOTRONIC 300-K Operations Instructions Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
Vitotronic 200 and 300-K Installation and Service
5693 976 - 04
20
Installation Sequence
Connecting the Central Fault Message Facility
Rated voltage 120V~
Rated current max. 2 A~
External Demand via Switching Contact
Connection options:
Connection at plug aVH
Extension EA1 (accessory, see page 93)
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Legend
A Dry contact
B Plug aVH of the control unit
When the contact is closed, burner operation is load-
dependent. The supply water is heated to the value set
in the coding address “9B” in the “General” group on the
Vitotronic 300 -K.
The supply water temperature is limited by this set
value and the electronic supply temperature maximum
limit (coding address “06” in the “Boiler” group on the
Vitotronic 200).
Legend
A Dry contact
B Extension EA1
Codes
Plug aVH No code required.
Extension EA1 Set “5D”, “5E” or “5F” in the “General”
group to 2.
Page view 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 95 96

Comments to this Manuals

No comments