Vitotronic 200 and 300-K Installation and Service
Commissioning
Checking Outputs Actuators and Sensors
Testing the relay – Vitotronic 300-K
The following relay outputs can be controlled subject to system design:
Display Explanation
“All actuators” OFF All actuators are switched off.
“Output 20” ON Output 20 enabled.
“Output 52” Open --
“Output 52” Neutr. --
“Output 52” Close --
“DHW tank primary pump” ON Output for DHW pump enabled.
“DHW circ. pump” ON Output for DHW recirculation pump enabled.
“Output 29” ON Output 29 enabled.
“Central fault mess.” ON --
“Htg circ. pump HC2” ON Output for heating circuit pump enabled (heating circuit with mixing valve M2).
“Mixing valve HC2” Open Output “Mixing valve open” enabled (heating circuit with mixing valve M2).
“Mixing valve HC2” Close Output “Mixing valve close” enabled (heating circuit with mixing valve M2).
“Htg circ. pump HC3” ON Output for heating circuit pump enabled (heating circuit with mixing valve M3).
“Mixing valve HC3” Open Output “Mixing valve open” enabled (heating circuit with mixing valve M3).
“Mixing valve HC3” Close Output “Mixing valve open” enabled (heating circuit with mixing valve M3).
“EA1 output 1” ON
Contact “P - S” on plug aBJ for extension EA1 closed.
“AM1 output 1” ON Output 1 enabled.
“AM1 output 2” ON Output 2 enabled.
“Solar circuit pump” ON
Output for solar circuit pump sF at solar control module, type SM1 enabled.
“Solar circ. pump min” ON
Output for solar circuit pump sF at solar control module, type SM1 switched
to minimum speed.
“Solar circ. pump max” ON
Output for solar circuit pump sF at solar control module, type SM1 switched
to maximum speed.
“SM1 output 22” ON
Output sS at solar control module, type SM1 enabled.
1. Press OK and
simultaneously for approx. 4 sec.
2. “Actuator test”
Information regarding the mixing valve motor rotational
direction
The supply temperature must rise when the mixing valve
opens. If the temperature drops, either the motor is
turning in the wrong direction or the mixing valve set is
incorrectly fitted (observe the mixing valve installation
instructions).
Vitotronic 200 sensor check
1. Press OK and
until service comes up.
2. Use to scroll to diagnosticsand select with OK.
3. Use to scroll to generaland select with OK.
4. Use to scroll to relevant sensorand press with
OK to view.
5. To exit press .
Actuators
1. Press OK and until service comes up.
2. Use
to scroll to actuator testand select with OK.
3. Use
to scroll to actuator to be tested and leave
highlight (actuator description will change from ‘OFF’
to ‘ON’).
4. When complete to exit press
.
Note: The service level is automatically exited after 30
minutes.