Vitotronic 200 and 300-K Installation and Service
5693 976 - 04
66
“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)
Coding in the factory set condition Possible change
F1:0 Slab curing function disabled. (Not used) F1:1
to
F1:6
Slab curing function adjustable in accordance
with 6 optional temperature/time profiles
(Not used)
F1:15 Constant supply temperature 68° F (20°C)
(Not used)
F2:8 Time limit for party mode or external heating
program changeover via pushbutton: 8 h
*2
.
Note: Observe settings of coding addresses
“5D”, “5E”, “5F” in the “General”
group, as well as “D5” and “D8” in the
“Heating circuit...” group.
F2:0 No time limit
*2
.
F2:1
to
F2:12
Time limit adjustable from
1 to 12 h
*2
.
F8:-5 Temperature limit for terminating reduced
mode 23°F (-5ºC), see example on page 84.
Observe the setting of coding address “A3”.
F8:+10
to
F8:-60
Temperature limit adjustable from
+50 to -76°F (+10 to -60°C)
F8:-61 Function disabled
F9:-14 Temperature limit for raising the reduced set
room temperature 7°F (-14ºC),
see example on page 84.
F9:+10
to
F9:-60
Temperature limit for raising the set room
temperature to the value selected for standard
mode adjustable from +50 to -76°F
(+10 to -60°C)
FA:20 Raising the set boiler water temperature
or the set supply temperature when
changing from operation with reduced room
temperature to operation with standard room
temperature, by 20%. See example on page
84.
FA:0
to
FA:50
Temperature rise adjustable from 0 to 50%
FB:60 Duration for raising the set boiler water
temperature or the set supply temperature
(see coding address “FA”) 60 min.
See example on page 84.
FB:0
to
FB:300
Duration adjustable from 0 to 300 min.
*2
Party mode ends automatically in the “Heating and DHW” program, when the system changes over to operation with
standard room temperature.
Coding 2 Vitotronic 300-K