Vitotronic 200 and 300-K Installation and Service
5693 976 - 04
48
Coding 2 Vitotronic 200
Coding
Coding in the factory setting Possible change
01:2 Do not adjust! -- --
04:1 Minimum burner pause subject
to the boiler load (specified by
boiler coding card)
04:0 Minimum burner pause set
permanently (specified by boiler
coding card).
06:... Maximum limit of the boiler
water temperature, specified
in °C by the boiler coding card
06:20
to
06:127
Maximum limit of the boiler water
temperature within the ranges
specified by the boiler.
07:1 Boiler number in multi boiler
systems
07:2
to
07:8
Boiler number 2 to 8 in multi-
boiler systems.
08:... Maximum burner heating output
in kW in the case of a multi
boiler system
08:0
to
08:199
Maximum burner heating output
adjustable from 0 to 199 kW
(limited by boiler specific
parameters) in steps of 1 kW.
0D:0 Do not adjust! -- --
0E:0 Do not adjust! -- --
13:1 Do not adjust! -- --
14:1 Do not adjust! -- --
15:1 Do not adjust! -- --
21:0 No service interval (hours run)
selected
21:1
to
21:100
Number of hours run before the
burner should be serviced is
adjustable from 100 to 10,000 h
One adjusting step 100 h.
23:0 No time interval for burner
service
23:1
to
23:24
Interval adjustable from 1 to 24
months.
24:0 No “Service” display 24:1 “Service” display (the address is
automatically set and must be
manually reset after a service has
been carried out).
28:0 No burner interval ignition 28:1
to
28:24
Interval adjustable from 1 hour
to 24 hours. The burner is force
started once every 30 seconds
(only when operating with LPG).
2E:0 Do not adjust! -- --
2F:0 Venting program/fill program
disabled
2F:1 Venting program enabled.
2F:2 Fill program enabled.
30:3 When changing from a single
boiler to a multi boiler operation,
the coding address may
automatically reset to 30:3. To
prevent continuous boiler pump
operation, adjust the coding
address for each boiler to 30:0.
30:0 Coding address should be set
to 30:0, if not adjust to 30:0
31:...
NOT USED
Set speed in % of the internal
circulation pump when operated
as boiler circuit pump, specified
by the boiler coding card
31:0
to
31:100
Set speed adjustable from
0 to 100%.
38:0 Status burner control unit:
Operational (no fault)
38:0 Status burner control unit: Fault.
“Boiler” Group