Vitotronic 200 and 300-K Installation and Service
“Heating Circuit 1, Heating Circuit 2, Heating Circuit 3” Group (continued)
Coding in the factory set condition Possible change
Start temperature raising
F8:-5 Temperature limit for terminating reduced mode
23°F (-5ºC), see example on page 83.
Observe the setting of coding address “A3”.
F8:+10
to
F8:-60
Temperature limit adjustable from
+50 to -76°F (+10 to -60°C)
F8:-61 Function disabled
End temperature raising
F9:-14 Temperature limit for raising the reduced
set room temperature 7°F (-14ºC),
see example on page 84.
F9+10
to
F9:-60
Temperature limit for raising the set room
temperature to the value selected for standard
mode adjustable from +50 to -76°F
(+10 to -60°C)
Set supply temperature increase
FA:20 Raising the set boiler water temperature
or the set supply temperature when changing
from operation with reduced room temperature
to operation with standard room temperature,
by 20%. See example on page 84.
FA:0
to
FA:50
Temperature rise adjustable from 0 to 50%
Duration set supply temperature increase
FB:30 Duration for raising the set boiler water
temperature or the set supply temperature
(see coding address “FA”) 60 min.
See example on page 82.
FB:0
to
FB:150
Duration adjustable from 0 to 300 min.;
1 step
2 min.
Coding 1 Vitotronic 300-K