Vitotronic 200 and 300-K Installation and Service
Commissioning
Checking Outputs on Actuators and Sensors (continued)
Standard room temperature
Example 1: Adjustment of the standard room temperature
from 68 to 79°F (20 to 26°C)
Adjustment of the standard room temperature:
Reduced room temperature
Example 2: Adjustment of the reduced room temperature
from 37 to 57°F (3 to 14°C)
Adjustment of the reduced room temperature:
Refer to the Operating Instructions
Refer to the Operating Instructions
Adjusting the set room temperature
Legend
A Boiler water temperature or supply temperature
B Outside temperature
C Set room temperature
D Heating circuit pump “Off”
E Heating circuit pump “On”
Legend
A Boiler water temperature or supply temperature
B Outside temperature
C Set room temperature
D Heating circuit pump “Off”
E Heating circuit pump “On”
230 °F
(110 °C)
79 °F
(26 °C)
68 °F
(20 °C)
-4 °F
(-20 °C)