Start-up
91
Steps (continued)
7. Match the coding addresses (continued)
10. Set the established values in coding
level 1.
See page 115 for coding 1.
Address
Setting of
05 the partial output (see point 8) as a percentage proportion of the
max. output; e.g.
partial output: 170 kW
max. output: 210 kW
170 kW
210 kW
x100 % = 81 %
08 units and tens digits of the maximum output established in point
4: e.g. max. output: 210 kW – here set: 10
09 hundreds digit of the maximum output established in point 4: e.g.
max. output: 210 kW – here set: 2
0A the basic output (see point 6) as a percentage proportion of the
max. output; e.g.
basic output: 70 kW
max. output: 210 kW
70 kW
210 kW
x100 % = 33 %
15 the operating time in seconds established in point 5
Please note:
You will find details of other possible settings in the sections entitled
”Coding 1” and ”Coding 2” (see page 115 and 117).
5351 338 v1.6
Comments to this Manuals