Coding 2 (continued)
Overview of all codings (continued)
Coding as per
factory setting
Address: Value
Function New coding
Address:
Value
Possible change
88: 0 General Temperatures displayed in Celsius 88: 1 Temperatures displayed in
Fahrenheit
8A:175 General Display of codings which can be set
for the system type concerned
8A:176 All codings displayed regardless of
system type and equipment
installed
92:165 General Do not Adjust! Is only displayed if
8A:176 is coded
93: 0 General Central fault indication in emissions
test mode/service display not
effective for central fault
93: 1 Central fault indication in
emissions test mode/service
display effective for central fault
94: 0 General Without plug-in adaptor for external
safety equipment
94: 2 With plug-in adaptor for external
safety equipment; recognized
automatically
98: 1 General Viessmann system number
(in conjunction with monitoring of
several systems within one LON BUS
system)
98: 2
to
98: 5
System number
selectable from 1 to 5
9b: 0 General Input aVH released 9b: 1
to
9b:127
Set-point supply temperature
selectable via plug aVH from 1 to
127°C / 261°F with external
request
9C: 20 General Monitoring of LON participants:
If a participant does not answer
b
a
c
k
,
d
e
f
a
u
l
t
v
a
l
u
e
s
s
e
t
w
i
t
h
i
n
t
h
e
9C: 0 No monitoring
b
a
c
k
,
d
e
f
a
u
l
t
v
a
l
u
e
s
s
e
t
w
i
t
h
i
n
t
h
e
control unit are used for the first 20
minutes. Then an error message is
transmitted.
9C: 1
to
9C: 60
Time selectable
from 1 to 60 minutes
9d: 0 General Without Input Module
0 to 10V
9d: 1 With Input Module 0 - 10V;
will be recognized automatically