Connection of the Return Temperature Sensor
Strap-on temperature sensor and immersion temperature sensor
For measuring the boiler return
and return temperature.
Electrical connection
The sensor is inserted in socket
”17A” or ”17B” on the boiler
control.
Check the sensor
1. Disconnect plug aJA or aJB
in the terminal compartment of
the boiler control.
2. Measure resistance of sensor at
terminals ”1” and ”2” of the plug.
Return
temperature
in °C / °F
Resistance
in
30 / 86
40 / 104
60 / 140
569
592
643
3. Compare the value measured with
the current temperature. If the
value differs significantly, check
installation and, if necessary,
replace sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
during operation: 0 to + 100°C
32 to + 212°F
during storage and transport:
-20 to + 70°C
-4 to + 158°F