System Components (continued)
TUV button, Part No. 7819 314
For checking the fixed high limit.
See description on page 86.
Fixed high limit, Part No. 7820 036
Type STW 56.10525.570, make: EGO, DIN STB (STW) 106095
or
EM-80-V-TK/b7-1 60002843, make: Juchheim, DIN STB 82699
The fixed high limit has a factory setting of 120°C / 248°F.
Electromechanical temperature switch based on the liquid expansion principle
with interlock
Intrinsically safe; interlocking also takes place if the capillary tube is leaking or
if ambient temperatures are below –10°C / 14°F
Limits the boiler water temperature to the maximum permissible value by
cutting out and interlocking
Can be adjusted with the slotted screw A at the rear of the unit to 110 and
99 °C / 230 and 210 °F (cannot be reset to 120°C / 248 °F once adjusted)
Reset unit by pressing the reset button E on the front of the programming
unit if the temperature has fallen approx. 15 K below the shut down temperature
Central fastening M 10, capillary 3600 mm long
Tests:
Electrical to VDE 0701 standard
Functional check via TEST button
Adjustable high limit, Part No. 7817 531
Type TR 55.18029.020, make: EGO, DIN TR 110397
or
EM-1-V-TK/b1 60002846, make: Juchheim, DIN TR 77798
The adjustable high limit has a factory setting of 95°C / 203°F
Electromechanical temperature switch based on the liquid expansion principle
Controls the maximum boiler water temperature (e.g. in emissions test mode)
Can be adjusted to 100 and 110°C / 212 and 230°F by altering the setting
of the stop dial or by removing the cams
Set the lower limit at least 20°C / 36°F higher than the domestic hot water
temperature, the upper limit at least 15°C / 27°F lower than the fixed high limit.
Adjusting shaft 6 mm / 0.27 inches, flat topped
Adjusting knob pushed onto shaft from front
Capillary 3600 mm / 141.7 inches long
Sensor 3 mm / 0.1inches thick, 180 mm / 7.1inches long
Tests:
Electrical to VDE 0701 standard
Functional check via emissions test mode
5351 338 v1.6