Additional information
123
Coding 2 (continued)
Overview of all codings (continued)
Coding as per
factory setting
Address: Value
Function New coding
Address:
Value
Possible change
62: 10 DHW Circulation pump with run-on time of
10 minutes
62: 0 Circulation pump without run-on
time
62: 1
to
62: 15
Run-on time variable from 1 to 15
minutes
67: 40 DHW With Vitosolic:
67: 0 Without 3rd DHW set-point
Reloading suppression will be active
above set temperature. DHW tank is
heated only by solar heating system.
67: 1
to
67: 95
Input of a 3
rd
set DHW set-point
temperature; adjustable
from 1 to 95˚C / 34 to 203˚F
63: 0 DHW Without additional function for
domestic hot water heating
63: 15 Twice per day
63: 0 DHW Without additional function for
63: 1 Additional function: Once per day
domestic hot water heating
63: 2
to
63: 14
Every 2 days
to
Every 14 days
68: 8 DHW In conjunction with 2 tank
temperature sensors with the DHW
heating:
Switch-off point of tank heating at
setpoint value x 0.8
68: 2
to
68: 10
Factor adjustable from 0.2 to 1
per 1 increment = 0.1
69: 7 DHW In conjunction with 2 tank
temperature sensors with the DHW
heating:
Switch-on point of tank heating at
setpoint value x 0.7
69: 1
to
69: 9
Factor adjustable from 0.1 to 0.9
per 1 increment = 0.1
76: 0 General Without LON communication module
76: 1 With LON communication module;
recognized immediately
76: 2 With Viessmann 2-wire BUS
communication module; recognized
immediately
77: 1 General LON participant number 77: 2
to
77: 99
LON participant number selectable
from 1 to 99
Please note:
Each number may be assigned
once only.
78: 1 General LON communication released 78: 0 LON communication blocked
79: 0 General Control unit is not error manager 79: 1 Control unit is error manager
80: 1 General With 5 seconds time delay for fault
80: 0 Without time delay
message
80: 2
to
80:199
Time delay adjustable between
10 and 995 seconds;
1 increment = 5 seconds
5351 338 v1.6