Functional description
105
Boiler Temperature Control
Brief description
The boiler water temperature is
controlled by switching the burner on
and off.
The set-point boiler water temperature
value is determined by the set-point
supply temperature values of the boiler
circuit (A1), the heating circuits with
mixing valve (from Vitotronic 050) and
the set-point supply temperature value
preset via coding address ”9b” as well
as the set-point domestic hot water
temperature, and is dependent on the
boiler and the heating and control
facilities installed.
In conjunction with Therm-Control:
The set-point boiler water temperature
is increased when the temperature falls
below the set-point value on the sensor
of the Therm-Control.
Coding addresses which influence
the boiler temperature control
02 to 06, 08 to 0b, 13 to 1C.
Functions
The boiler water temperature is
measured via a multiple sensor well by
three sensors separately:
Fixed high limit FHL
(liquid expansion)
Adjustable high limit AHL
(liquid expansion)
Boiler temperature sensor BTS
(change in resistance PT 500)
Upper limits of control range
Fixed high limit FHL
110°C / 230°F, can be adjusted to
100°C / 212 or 230°F
Adjustable high limit AHL
95°C/ 203°F, can be adjusted to
100°C / 212°F
Electronic maximum limit
Setting range: 20 to 127°C /
68 to 261°F
The maximum limit for the boiler
water temperature is defined in
coding address ”06”.
Lower limit of control range
The control unit regulates the boiler
water temperature in normal
operation and in the frost protection
mode according to the boiler
concerned (boiler coding card).
Control sequence
Boiler temperature falls
The burner override signal is set for a
boiler water temperature setpoint value
of –2°C / -4°F, and the burner starts
its own monitoring program. Depending
on the range of additional control
facilities and the method of firing,
burner override can be delayed by a
few minutes.
Boiler temperature rises
The switch-off point of the burner is
defined by the switch-off differential
(coding address ”13”).
5351 338 v1.6