System Components (continued)
Input Module 0 to 10 V, Part No. 7134 561
From software version 7 of Vitocontrol-S, VD2/CT3, the Input Module can be connected (software version via scan 2:
1st digit, display 7).
For external control of the boiler/supply temperature via a 0 to 10VDC signal
10 to 100˚C or 30 to 120˚F
50 to 212˚C or 86 to 248˚F
or
to signal reduced mode and regulate a heating circuit pump to a lower speed.
Power connection
aVF 0 to 10VDC input
aVG KM BUS to control unit
aBJ Potential free output contact
A Power supply
(provide disconnect if required by
code)
B DIP switch (see table)
DIP switch
Function
1 to 3:
1:
2:
3:
4:
4:
OFF
ON
ON
ON
ON
OFF
Switch for pre-set value
Reduced mode – system circuit A1
Reduced mode – mixing valve circuit M2
Reduced mode – mixing valve circuit M3
Pre-set value default 10 to 100˚C / 50 to 212˚F
Pre-set value default 30 to 120˚C / 86 to 248˚F
Please note:
Amongst switches 1 to 3, only one switch may be set to ON.
Resetting codings to the factory setting
1. Press w and rw simultaneously
for approx. two seconds, until the
first two arrows appear in the
display.
2. Press D.
5351 338 v1.6
OFF
A
Electronics