Troubleshooting
102
Diagnosis (continued)
Faults with fault display on the programming unit (continued)
F
a
u
l
t
code in
display
Behaviour of system
Cause of fault Action
aa
Controlled operation Therm-Control configuration
error:
plug aJA of
Therm-Control temperature
sensor not inserted
Insert plug aJA
On Vitocrossal:
Check that coding ”0d: 0” is set.
ab
Controlled operation, DHW tank
may be cold
DHW heating
configuration error:
Coding ”55: 3” is set, but
plug aJB is not inserted
and/or
coding ”4C: 1” and ”4E: 1”
not set
Insert plug aJB and check coding
aCc
Controlled operation Return temperature sensor
configuration error:
Coding ”0C: 1” is set, but
plug aJA is not inserted
and/or
coding ”4E: 0” is not set
Insert plug aJA and check coding
aCd
Controlled operation Butterfly valve
configuration error:
Coding ”0C: 2”, ”0C: 3” or
”0C: 4” is set,
and
coding ”4E: 1” is set
If butterfly valve is installed:
Set coding ”4E: 0”
If no butterfly valve is installed:
Set coding ”0C: 0” or ”0C: 1”
b0
Controlled operation Short circuit
Flue gas temperature sensor
Check flue gas temperature sensor
(see page 45)
b1
Controlled operation Communication error
Programming unit
Check connections, if necessary
replace programming unit
b4
Emissions test mode Internal fault Check electronics board
b5
Controlled operation Internal fault Check electronics board
b6
Operation at constant temperature Invalid hardware code Check the control software circuit
board and confirm the coding address:
- Enter coding 2 (see page 101
for instructions).
- Change code 8A to 176.
- Confirm coding 92:160
b7
Boiler controlled on basis of
adjustable high limit
Internal fault
Boiler coding card
Insert boiler coding card or replace
if defective (see page 35)
b8
Controlled operation Open circuit
Flue gas temperature sensor
Check flue gas temperature sensor
(see page 45)
bf
Controlled operation Incorrect LON communication
module
Replace LON communication
module
c1
Boiler cools down External safety equipment Check connection of plug
aBÖ
Check external safety
equipment
5351 338 v1.6