137
Note
Codes that have not been assigned due
to the heating system equipment level or
the setting of other codes are not dis-
played.
1. Press OK and simultaneously for
approx. 4 s.
flashes on the display.
2.
With , select 1 for coding level 1
and confirm with OK.
"I" flashes on the display for the cod-
ing addresses in category 1.
3. Select the category of the required
coding address with / :
1: "General"
2: "Boiler"
3: "DHW"
4: "Solar"
6: "All codes std device". In this
category, all coding addresses of
coding level 1 are displayed in
ascending order.
Confirm selected category with OK.
4. Select coding address with / .
5. Select value according to the follow-
ing tables with / and confirm with
OK.
6. If you want to reset all codes to
their delivered condition:
Select "7" with and confirm with
OK.
When flashes, confirm with OK.
Note
This also resets codes from coding
level 2.
7. Exit coding level 1: Press .
8. Exit the service level: Press to
select
9
.
9. Confirm with OK.
"OFF" flashes.
10. Confirm with OK.
Note
The service level is automatically
exited after 30 minutes.
Code 1
Calling up coding level 1
5600 634 GB
Service