Fault codes
Displayed
fault code
System characteris-
tics
Cause Measures
0F Control mode. Service
"0F" is only dis-
played in the fault
history.
Service required
Note
After servicing, set code
"24:0".
30 With DHW cylinder:
Circulation pump
for cylinder heating
on; boiler is main-
tained at set cylin-
der temperature.
Without DHW cylin-
der:
Boiler is regulated
by the temperature
controller.
Short circuit, boiler
water temperature
sensor.
Check the boiler water
temperature sensor (see
page 169).
38 With DHW cylinder:
Circulation pump
for cylinder heating
on; boiler is main-
tained at set cylin-
der temperature.
Without DHW cylin-
der:
Boiler is regulated
by the temperature
controller.
Lead break, boiler
water temperature
sensor.
Check the boiler water
temperature sensor (see
page 169).
Troubleshooting
Fault display
(cont.)
5600 634 GB