Address Meaning Setting
09:... Hundreds of the maximum burner
output
Example: Max. burner output: 225
kW – select: 2
15:... Modulation range runtime Calculate servomotor runtime (s)
between base load and max. burner
output
0A:... Ratio of output base load to maxi-
mum burner output in percent
Example: Output burner stage 1
135 kW
Max. burner output: 225 kW
(135 kW: 225 kW)
100 % = 60 %
05:...
Ratio of partial output at of the
servomotor runtime to maximum
burner output in percent
Example: Partial output 171 kW
Max. burner output: 225 kW
(171 kW: 225 kW)
100 % = 76 %
Checking actuators and sensors
Testing relays
1. Press OK and simultaneously for
approx. 4 s.
flashes on the display.
2. With select and confirm with
OK.
3. Select required actuator with / (see
following table).
The display shows the number for the
activated actuator and "ON".
Commissioning
Matching the coding addresses to the system…
(cont.)
5600 634 GB