Coding in the delivered condition Possible change
3E:2 Boiler circuit pump is star-
ted on "External blocking"
signal
3F:0 Boiler circuit pump stays
in control mode on "Ex-
ternal demand" signal
3F:1 Boiler circuit pump is stop-
ped on "External demand"
signal
3F:2 Boiler circuit pump is star-
ted on "External demand"
signal
4b:0
Function input lH: Room
thermostat (Vitotrol 100,
only for constant temper-
ature control units)
4b:1 External demand
4b:2 External blocking
51:0 System with low loss
header:
boiler circuit pump is al-
ways started when there
is a heat demand
51:1 System with low loss head-
er:
when there is heat de-
mand, the boiler circuit
pump will only be started if
the burner is running.
Circulation pump stops on
expiry of the run-on time.
51:2 System with heating water
buffer cylinder:
when there is heat de-
mand, the boiler circuit
pump will only be started if
the burner is running.
52:0 Without flow temperature
sensor for low loss head-
er
52:1 With flow temperature sen-
sor for low loss header (au-
tomatic recognition)
53:1
Function terminal sK of
the internal extension:
DHW circulation pump
53:0
Function terminal sK: cen-
tral fault message
53:2
Function terminal sK: ex-
ternal heating circuit pump
(heating circuit 1)
53:3
Function terminal sK: ex-
ternal circulation pump for
cylinder heating
54:0 Without solar thermal
system
54:1 With Vitosolic 100 (auto-
matic recognition)
Code 2
General/group "1"
(cont.)
5585 174 GB
Service