Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the standard set room temper-
ature
Operating instructions
Reduced set room temperature
+20 14 5
90
-20
D E
A
C
B
Example 2: Adjustment of the reduced
set room temperature from 5 °C to
14 °C
A
Boiler water temperature or flow
temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the reduced set room temper-
ature
Operating instructions
Changing the slope and level
Individually adjustable for each heating
circuit.
A
B
Boiler water or
flow temperature in °C
90
+20 -20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel
offset of the heating curve)
Extended menu:
1. å
2. "Heating"
3. Select heating circuit.
4. "Heating curve"
5. "Slope" or "Level"
6. Select heating curve according to the
system requirements.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)