Checking the flue gas non-return device
A
B
1.
Undo 3 screws and remove fan A.
2. Remove flue gas non-return device
B
.
3. Check the damper and gasket for dirt
and damage. Replace if required.
4.
Refit flue gas non-return device B.
5.
Refit fan A and secure with 3
screws.
Torque: 3.0 Nm
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5585 174 GB