Connecting the control unit to the LON system - only for weather-
compensated control units
The LON communication module
(accessories) must be plugged in.
Installation instructions
LON communication module
Note
The data transfer via LON can take sev-
eral minutes.
Single boiler system with Vitotronic
200-H and Vitocom 200 (example)
Set the LON subscriber numbers and
further functions via code 2 (see the fol-
lowing table).
Note
In the same LON system, the same sub-
scriber number must not be allocated
twice.
Only one Vitotronic may be program-
med as fault manager.
All coding addresses in the table are listed in the "General" group.
Boiler control unit Vitotronic 200-H Vitotronic 200-H Vitocom
LON LON LON
Subscriber no. 1,
Code "77:1".
Subscriber no. 10,
Code "77:10".
Subscriber no. 11,
Set code "77:11".
Subscriber
no. 99.
Control unit is fault
manager,
Code "79:1".
Control unit is not
fault manager,
Code "79:0".
Control unit is not
fault manager,
Code "79:0".
Device is fault
manager.
Control unit transmits
the time,
Code "7b:1".
Control unit receives
the time,
Set code "81:3".
Control unit receives
the time,
Set code "81:3".
Device re-
ceives the
time.
Control unit transmits
outside temperature,
Set code "97:2".
Control unit receives
outside tempera-
ture,
Set code "97:1".
Control unit receives
outside tempera-
ture,
Set code "97:1".
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5772 909 GB
Service