Max. heating output setting
The maximum output for heating oper-
ation can be limited. The limit is set via
the modulation range. The max. adjust-
able heating output is limited upwards by
the boiler coding card.
Weather-compensated control unit Constant temperature control unit
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Service functions"
3. "Max. output"
4. "Change?" Select "Yes".
A value is shown on the display (e.g.
"85"). In the delivered condition, this
value represents 100 % of rated heat-
ing output.
5. Set the required value.
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2.
Select "3" with Ú and confirm with
OK.
A value flashes on the display (e.g.
"85") and "
A
" appears. In the deliv-
ered condition, this value represents
100 % of rated heating output.
3. Select required value and confirm with
OK.
Tightness test for balanced flue system (annular gap check)
A
A
Combustion air aperture
For balanced flue systems tested
together with the wall mounted gas fired
boiler, the requirement for a tightness
test during commissioning by the flue
gas inspector is not applicable.
We recommend that your heating engi-
neer carries out a simple leak/tightness
test during the commissioning of your
system. For this, it would be sufficient to
check the CO
2
or O
2
concentration in the
combustion air at the annular gap of the
balanced flue pipe.
The flue pipe is deemed to be gas-tight
if the CO
2
concentration in the combus-
tion air is no higher than 0.2 % or the
O
2
concentration is at least 20.6 %.
If actual CO
2
values are higher or O
2
val-
ues are lower, then pressure test the flue
pipe with a static pressure of 200 Pa.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)