Viessmann Type B2HA Operations Instructions Page 179

  • Download
  • Add to my manuals
  • Print
  • Page
    / 188
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 178
179
Settings and actual values Set value Commis-
sioning
Mainte-
nance/
Service
Date
Signature
Static pressure mbar
kPa
≤ 57.5
≤ 5.75
Supply pressure (flow pres-
sure)
= for natural gas E
mbar
kPa
17.4-25
1.74-2.5
= for natural gas LL
mbar
kPa
17.4-25
1.74-2.5
= for LPG
mbar
kPa
42.5-57.5
4.25-5.75
Tick gas type
Carbon dioxide content
CO
2
For natural gas
At lower heating output % by vol. 7.5-9.5
At upper heating output % by vol. 7.5-9.5
For LPG
At lower heating output % by vol. 8.8-11.1
At upper heating output % by vol. 8.8-11.1
Oxygen content O
2
At lower heating output % by vol. 4.0-7.6
At upper heating output % by vol. 4.0-7.6
Carbon monoxide content
CO
At lower heating output ppm < 1000
At upper heating output ppm < 1000
Commissioning/service reports
Commissioning/service reports
5772 909 GB
Service
Page view 178
1 2 ... 174 175 176 177 178 179 180 181 182 183 184 ... 187 188

Comments to this Manuals