209
The influence of room temperature hook-
up can be selected, subject to a room
temperature sensor being installed and
room temperature hook-up being ena-
bled (see page 209).
The higher the value, the greater the
influence of the room temperature on the
set flow temperature of the relevant heat-
ing circuit with weather-compensated
control.
Delivered condition 10
Setting range 0 to 50
200B Room temperature hook-up (heating circuits)
"Room temperature hook-up 200B"
This parameter determines the condi-
tions under which the set flow tempera-
ture with weather-compensated control
should be corrected by the room influ-
ence.
Valu
e
Explanation
"0" Weather-compensated control
without room influence. Set flow
temperature is not corrected.
"1" Weather-compensated control
with room influence only for
"Reduc." operating status.
Valu
e
Explanation
"2" Weather-compensated control
with room influence only for "Nor-
mal" operating status.
"3" Weather-compensated control
with room influence for
"Reduc." and "Normal" operat-
ing statuses.
Delivered condition 3
Setting range 0 to 3
200E Maximum set flow temperature
"Maximum flow temperature 200E"
Maximum permissible set flow tempera-
ture for a heating circuit.
Parameter group heating circuits/cooling circuit
200A Influence of room temperature hook-up
(cont.)
5442 829 GB