Function description
Boiler water temperature control (cont.)
Functions
The boiler water temperature is
recorded by three sensors
separately, which are inserted into a
multiple sensor well:
H High limit safety cut−out (STB)
(liquid expansion)
H Control thermostat TR
(liquid expansion)
H Boiler water temperature sensor KTS
(change in resistance PT 500)
Upper control range limits
H High limit safety cut−out STB
120 ºC, adjustable to 110 or 100 ºC
H Thermostat TR95ºC, adjustable to
100 or 110 ºC
H Electronic maximum limit
Setting range: 20 to 127ºC
Changes via coding address"06".
Lower control range limit
In standard mode and when frost
protection is active, the control unit
regulates the boiler water
temperature subject to the
respective boiler.
Control sequence
Boiler goes cold
(set value 2 K)
The burner start signal is set at the
set boiler water temperature less 2 K,
and the burner starts its own
monitoring program.
The burner start may be delayed by a
few minutes subject to the number
of the auxiliary circuits and the
combustion type.
Boiler heats up
The burner shutdown point is
determined by the shutdown
differential (coding address "13").
5862730GB