Viessmann VITOTRONIC 100 GC1B Installation Manual Page 97

  • Download
  • Add to my manuals
  • Print
  • Page
    / 164
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 96
97
5793 309 - 04
Vitotronic 100, GC1B / Vitotronic 300-K, MW1B Installation and Service
Calling up operating data
1. Press OK and simultaneously for approx. 4 sec.
2. “Diagnosis”
3. Select required group, e.g. “General”.
Service Scans, Vitotronic 300-K
Scanning Operating Data
Operating data can be scanned in six areas (see
“Diagnosis” in the overview “Service menu”).
Operating data on heating circuits with mixing valves and
solar can only be scanned if the components are installed
in the system.
For further information on operating data, see chapter
“Brief scan”.
Note: “- - -” appears on the display if a sensor that has
been scanned is faulty.
Calling up the Service Menu
Service menu overview
Press OK and
simultaneously for approx. 4 sec.
“Coding level 2” is only displayed if this level has been
enabled:
Resetting operating data
Saved operating data (e.g. hours run) can be reset to 0.
The value “Adjusted outside temp” is reset to the actual
value.
1. Press OK and
simultaneously for approx. 4 sec.
2. “Diagnosis”
3. “Reset data”
4. Select required value or “All details”.
Press OK and simultaneously for approx. 4 sec.
Service
Diagnosis
Actuator test
Coding level 1
Brief scan
Coding level 2
Fault history
Service functions
Terminate service?
General
Heating circuit 1 HC1
Heating circuit 2 HC2
Heating circuit 3 HC3
DHW
Solar
Reset data
Participant check
Service PIN
Service reset