Viessmann VITODENS 200 WB2 Series Service Manual

Browse online or download Service Manual for Water heaters & boilers Viessmann VITODENS 200 WB2 Series. Viessmann VITODENS 200 WB2 Series Technical data [en] User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Vitodens 200, WB2-24C/24/32 Vitodens 200, WB2-44/60
(with preinstalled vent pipe adaptor)
VITODENS 200
Gas-fired wall-mounted condensing boiler
25to230MBH/7to67kW
Multi-boiler installation 344 to 920 MBH/
Vitodens 200
WB2 Series
Gas-Fired Wall-Mounted Condensing Boiler
with modulating MatriX-compact gas burner
for room air independent operation
(using a direct vent system and room air
dependent operation)
For Natural Gas and Liquid Propane
Heating input NG 25 to 230 MBH
7to 67kW
Heating input LP 25 to 214 MBH
7to 63kW
Technical Data Manual
Model Nos. and pricing: see Price List
5167 472 v3.2 11/2006
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - Technical Data Manual

Vitodens 200, WB2-24C/24/32 Vitodens 200, WB2-44/60(with preinstalled vent pipe adaptor)VITODENS 200Gas-fired wall-mounted condensing boiler25to230MBH

Page 2 - Product Information

Heating Circuit Pumps/DHW ProductionPump selection must be based on accuratesystem flow and pressure drop calculations(incl. DHW sizing). Viessmann of

Page 3 - Cross-Section

DHW Production354045505560656 7 8 9 10 11 12 13 14Draw rate at tap (mixed water)DHW output temperature951041131221311401491.6 1.8 2.1 2.4 2.6 2.9 3.1

Page 4 - Vitodens 200

DHW Production12Domestic Hot Water Production via DHW Storage TankVitodens 200 boilers can be used inconjunction with the stand-alone DHWstorage tanks

Page 5

DHW Recirculation13DHW RecirculationDHW recirculation lines increase the level ofcomfort and convenience of the domestichot water supply and reduce wa

Page 6

Wall Mounting14Wall Mounting Information (up to model WB2 8-32)Required accessories for installation withoutDHW storage tankMounting bracketc/w mounti

Page 7 - Vitodens 200/Technical Data

Wall Mounting15Wall Mounting Information (model WB2 11-44 and up)The Vitodens 200 (model WB2 11-44 andup) comes with a template, which allowsyou to ea

Page 8 - Technical Data

Condensate Connection/Neutralization Unit16Condensate ConnectionInstall the condensate drain pipe with asuitable gradient.Discharge condensate from th

Page 9 - Heating Circuit Pumps

Venting OptionaStandard side wall venting layoutMax. wall thickness19.6”/500 mmCombustion air intakeFlue gas outleta = total vent length17Side Wall Ve

Page 10 - IMPORTANT

Venting Option18Vent termination location requirements (for installations in Canada)The vent must be installed observing localregulations in addition

Page 11 - DHW Production

Venting OptionEquivalent vent length calculation*119Equivalent Vent Length87º elbowVent pipe (3.3 ft./1 m)Vent pipe (1.65 ft./0.5 m)Vent termination*1

Page 12

Product Information2VITODENS 200The Vitodens 200 is a high-qualitycondensing boiler made of stainless steel,developed in accordance with the latestach

Page 13 - DHW Recirculation

Venting Option20Vertical Venting OptionVent pipe adaptorVent inspection tee/Elbow, 87° (1 per carton)Sliding couplingStraight pipe3.3 ft./1 m or1.65 f

Page 14 - Wall Mounting

Venting Option21Vent termination location requirementsThe vent must be installed observing local regulations in addition to National Codes, CAN/CSA-B1

Page 15

Venting OptionVent length “a”a22Equivalent Vent LengthEquivalent vent lengthBoiler model6-24C 6-24 8-32 11-44 15-60Maximum ventlength5” vent system6”

Page 16

Venting Option23Equivalent Vent Length (continued)Type of fittingEquivalent length87º elbow/87º inspection tee1.65 ft./0.5 m45º elbow 1 ft./0.3 mEquiv

Page 17 - Side Wall Venting Option

Venting Option24Single Wall Venting OptionPlease note that there is no basic vent kit available for this vertical vent system.See product literature s

Page 18

Venting Option25Vent termination location requirementsThe vent must be installed observing local regulations in addition to National Codes, CAN/CSA-B1

Page 19

Venting Option26General Installation ExamplesEnsure that the venting system is properlysupported; the Vitodens 200 boiler is notdesigned to support th

Page 20 - Vertical Venting Option

Venting Option27Maximum/Minimum Vent LengthMaximumventlengthBoiler model WB2 6-24C 6-24 8-32 11-44 15-60a (max. length)3” vent system4” vent systemft.

Page 21

Venting Option28Equivalent Vent LengthType of fitting Equivalent length90º elbow 3 ft./0.9 m45º elbow 2 ft./0.6 mEquivalent vent length calculation ex

Page 22

Electrical Connection29Electrical ConnectionPower SupplyThe Vitodens 200 is shipped with a PowerModule (up to model WB2 8-32) or with aPower/Pump Modu

Page 23

Product InformationCross-SectionVitodens 200, WB2 6-24C(25-91 MBH/7-27 kW) shown.Product may not be exactly as illustrated.3Fully modulating MatriX-co

Page 24 - Single Wall Venting Option

Control for Weather-Responsive Operation30Control for Weather-Responsive OperationBuilt into the Vitodens 200 boiler is a menu-driven programming unit

Page 25

Control for Weather-Responsive Operation31Heating Curve Adjustment (slope and shift)The control unit regulates the boiler watertemperature (= supply t

Page 26

Control for Weather-Responsive OperationAccessories32Control for Weather-Responsive OperationAccessoriesMixing Valve Actuator Accessory Kit,Part No. 7

Page 27

Control for Weather-Responsive OperationAccessories33Boiler Temperature Indication Unit,Part No. 7133 384Must be inserted into the control unit forwea

Page 28

Control for Weather-Responsive Operation/Vitodens 200Accessories34Room Temperature Sensor,Part No. 7133 379Separate room temperature sensor used inadd

Page 29 - Electrical Connection

Vitodens 200 Accessories35Accessories for Vitodens 200 (continued)The temperature sensor connection [TS]typically located at the top of the low-losshe

Page 30 - (continued)

Standard Equipment36Standard EquipmentThe Vitodens 200 gas-fired condensingboiler with Inox-Radial heat exchangersurfaces, modulating MatriX-compact g

Page 31

How the Vitodens 200 boiler operates... /Installation Examples37How the Vitodens 200 boiler operates...The MatriX burner blower and thecombination gas

Page 32 - Accessories

Installation Examples38System Layout 1Vitodens 200 (model WB2 6-24C) with a direct-connected heating circuitAV Air ventDCW Domestic cold waterDHW Dome

Page 33

Installation Examples39System Layout 2Vitodens 200 (up to model WB2 8-32) with...– DHW storage tank– one direct-connected heating circuit– one heating

Page 34

Vitodens 2004Technical DataCombi Series Standard heating boilerBoiler Model Model No. WB2 6-24C WB2 6-24 WB2 8-32 WB2 11-44 WB2 15-60Natural gasCSA in

Page 35 - Vitodens 200 Accessories

Installation Examples40System Layout 3Vitodens 200 (up to model WB2 8-32) with...– DHW storage tank– one heating circuit with mixing valve– one heatin

Page 36 - Standard Equipment

Installation Examples41System Layout 4Vitodens 200 (up to model WB2 8-32) with...– DHW storage tank– two heating circuits with a mixing valveAV Air ve

Page 37 - Installation Examples

Installation Examples42System Layout 5Vitodens 200 (up to model WB2 8-32) with...– direct-connected heating circuit– one heating circuit with system s

Page 38

Installation Examples43System Layout 6Vitodens 200 (model WB2 11-44 and up) with...– DHW storage tank and– one direct-connected heating circuitYAV Air

Page 39

Installation Examples44System Layout 7Vitodens 200 (model WB2 11-44 and up) with...– DHW storage tank– one heating circuit with mixing valve and syste

Page 40

Installation Examples45System Layout 8Vitodens 200 (model WB2 11-44 and up) with...– DHW storage tank– low-loss header– one heating circuit with mixin

Page 41

Installation Examples46System Layout 9Vitodens 200 (model WB2 11-44 and up) with...– DHW storage tank– two heating circuits with a mixing valveAV Air

Page 42

Installation Examples47System Layout 10Vitodens 200 (model WB2 11-44 and up) with...– DHW storage tank– low-loss header– multiple heating circuits wit

Page 43

Installation Examples48Installation ExampleMultiple Vitodens 200, WB2-44 or -60 installation (up to four boilers) with one boiler dedicated to DHW pro

Page 44

Installation Examples49System Design ConsiderationsIN THE COMMONWEALTH OF MASSACHUSETTS...-this product shall be installed by a licensed plumber or ga

Page 45

Vitodens 2005Combi Series Standard heating boilerBoiler Model Model No. WB2 6-24C WB2 6-24 WB2 8-32 WB2 11-44 WB2 15-60DimensionsOverall depthOverall

Page 46

505167 472 v3.2

Page 47

515167 472 v3.2

Page 48

Viessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • CanadaTel. (519) 885-6300 • Fax (519) 885-0887www.viessmann.ca • ma

Page 49 - System Design Considerations

Vitodens 20078”/1975 mm (from floor level, recommended)GC BRDR/DCW15”/380 mmBS10”/250 mmFFL5”/125 mm38”/965 mmBD37”/938 mm16”/406 mm(Depth)(Height)DS/

Page 50 - 5167 472 v3.2

Vitodens 200/Technical Data78”/1975 mm (from floor level, recommended)3”/75 mm12”/300 mmFFL(AV2”/50 mm53” / 1346 mm8½”/215 mm21¼”/(Height)73/8“/187 mm

Page 51

Technical DataPressure drop up to model WB2 8-32Pressure drop model WB2 11-44 and up01234567803.36.69.813.116.419.72326Supply head pressureft.m0 2.2 4

Page 52

Heating Circuit PumpsWith pump rotational speed set to 100% flow capacity (2700 rpm);see Coding Address 045 in the Vitodens 200Start-up/Service Instru

Comments to this Manuals

No comments